    Can I use this capped pipe for basement bath vent?
    I'm thinking about finishing up my basement, but not sure where to get access to the vent stack.

    After looking through the basement, I found this capped pipe (2" or 2 1/4") sticking out from the basement ceiling, does this look like the "Future Vent" that I should tap into for basement venting? If so, can I directly connect my basement toilet vent line to this pipe?

    Judging by location, this pipe seems to come down from wall between my kitchen and first floor bathroom.

    Thanks in advance for any suggestions.
    Attached Images
      
    puffmugs's Avatar
    puffmugs Posts: 184, Reputation: 21
    Junior Member
     
    #2

    Jul 20, 2012, 05:48 AM
    It appears to be a future vent. When roughing in a house with a basement we would always leave a future vent, in many areas in Ohio it was a code requirement. My answer would be yes, use it.
    lucaslc's Avatar
    lucaslc Posts: 16, Reputation: 1
    New Member
     
    #3

    Jul 20, 2012, 07:30 AM
    Thanks a lot for answering. I'm a newbie to plumbing.

    Do I need to cut the cap and tie this "Future Vent" into the soil stack (a few feet above basement floor), and then tie the toilet/sink vents at a higher point of this future vent line (a few feet above the connection of soil stack and future vent)?

    Please see attached simple sketch. I'm planning to use upflush toilets like saniflo, The leftest vetical line is the discharge line from marcerating pump. Any suggestions would be appreciated.
    Attached Files
  1. File Type: txt New Text Document.txt (353 Bytes, 103 views)
  2. lucaslc's Avatar
    lucaslc Posts: 16, Reputation: 1
    New Member
     
    #4

    Jul 20, 2012, 07:38 AM
    BTW, I forgot to mention this is in Illinois. And the house was built in 1995, I'm guessing by then a lot of houses are already putting in "Future" vents?
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #5

    Jul 20, 2012, 09:38 AM
    Looks like a dedicated vent line for a sewer lift pump. To you have a pit or stub out in the basement?
    lucaslc's Avatar
    lucaslc Posts: 16, Reputation: 1
    New Member
     
    #6

    Jul 20, 2012, 09:55 AM
    No pit or stub. This basement doesn't have basement bath rough in.
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #7

    Jul 20, 2012, 11:35 AM
    You said "no rough in " but you have a toilet . How does it vent and drain now?
    lucaslc's Avatar
    lucaslc Posts: 16, Reputation: 1
    New Member
     
    #8

    Jul 20, 2012, 11:40 AM
    No rough in, no existing toilet in basement. I'm planning to finish the basement with a bathroom, so was sketching the plumbing diagram.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #9

    Jul 20, 2012, 02:40 PM
    Hi Lucaslc

    So you are planning on installing a saniflo toilet and a sink (1/2 bath) or are you including a tub/shower as well?

    Either way, with the saniflo system you will want to tie the plumbing vents and the saniflo system vent together (at a minimum of 42" off the floor) and then connect the 2" vent to the future vent (or pit vent) you showed us.

    When you attempt to cut the cap off I would suggest drilling a hole in the cap and draining the pipe into a bucket as it should have some nasty rain water in it.

    Back to you...

    Mark
    lucaslc's Avatar
    lucaslc Posts: 16, Reputation: 1
    New Member
     
    #10

    Jul 20, 2012, 02:52 PM
    Mark,
    Thanks for the answer. That seems to be exactly what saniplus's manual shows.

    Here's what confuses me:
    If the future vent does have rain water, do I need to connect the future vent to the soil stack and then connect the bathroom vents to the future vent? You can see my previous post's attached txt file for my sketch.

    Or is it possible the so called "future" vent is simply a stud that extends from the first floor plumbing vent? If that's the case, I should still be able to use it, but it's not directly leading up to the roof so shouldn't have rain water issue, right?

    Thanks.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #11

    Jul 20, 2012, 02:58 PM
    Hi Lucas

    In most states, you will NOT need to connect that future vent to the plumbing stack... just run as a 2" vent to the new bathroom group.

    In terms of the rainwater, the future vent should have some rainwater in it as all vents have fittings that are installed upside down and directed in such a manner as to direct water flow (rain water) from the roof to the drains in the basement.

    If you hook this vent to the sink drain (and saniflo pump) then the rain water that will naturally flow will just flow into the sink drain and into the saniflo pump.

    Mark
    lucaslc's Avatar
    lucaslc Posts: 16, Reputation: 1
    New Member
     
    #12

    Jul 20, 2012, 03:04 PM
    Mark,

    Thanks a lot for the clarification, it clears my head now!
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #13

    Jul 20, 2012, 03:09 PM
    Pop back anytime!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Exhausting a bath fan through a waste vent pipe? [ 20 Answers ]

I am installing an exhaust fan in my upstairs bath. An easy and close by exhaust source would be the existing plumbing vent. Can I tee into this vent without worrying about odor problems in the bath? I would tap into it just below where it goes through the roof. The existing vent is close to...

Can I connect a capped plumbing vent pipe in my basement to main septic drain? [ 9 Answers ]

Not much experience with plumbing systems, but I'll try to be as clear as I can. Our basement is not finished, but is roughed in for a full bath. There is a plumbing vent coming down from the first floor into the basement area - it extends straight down about 8 inches and is capped off. I assume...

Basement Bath Vent sizing [ 6 Answers ]

I am adding a basement bathroom in a 1926 house. The mainline is cast iron. I plan on cutting the ci below grade and adding a backwater valve. The house is two story with a basement. I currently have a 1.5" vent from the old laundry tray in the area. My question: Can I use the 1.5" vent to...

Vent for basement bath room [ 7 Answers ]

I want to install a bath room with toilet, tub/shower and sink in my unfinished basement. There are three pipes combing from ground. But there is not vent combing down from the basement roof. Also, I have three contractors looked at my basement. I got confused with what they said. The...


View more questions Search